3 core flat cables

3 core Winding Wire

For trouble free working, the connecting cables for submersible pumps motors are just as important as winding wires. JSB 3 core flat cables are manufacturer keeping in mind severe & difficult conditions in which they are required to operate.

Conductors :
The conductors, drawn from bright electrolyte grade copper, are annealed and bunched together.

Insulation :
Bunched conductors are insulated with specially formulated, in-house developed PVC compound with high insulation resistance values. The insulation process is carried out on modern high speed extrusion lines with high accuracy, ensuring consistency in performance.

Sheath :
The insulated core are laid up to form the core assembly. The outer sheath of the cable is made from a special grade of abrasion resistant to PVC compound impervious to water, grease, oil etc. This sheathing facilitate not only ease in stripping but also to withstand mechanical abrasion while in use.

Overall Dimensions
Area (Nom) Sq.mm Number Size of Wire in mm Thickness (Nom.) mm Core Dia(Nom.) mm Thickness (Nom.) mm Width "W" mm Thickness "T" mm Cond Resist. @20°C (Max) Ohm/Km Current Carrying capacity @40°C Amps
1.5 22/.3 0.8 3.25 1.15 12.8 6.0 13.30 14
2.5 36/.3 0.9 3.90 1.15 14.6 6.4 7.98 18
4.0 56/.3 1.0 4.65 1.15 17.2 7.4 4.95 26
6.0 84/.3 1.0 5.30 1.15 18.7 7.9 3.30 31
10.0 140/.3 1.0 6.60 1.40 23.7 9.9 1.91 42
16.0 226/.3 1.0 8.20 1.40 28.0 11.4 1.21 57
25.0 354/.3 1.2 10.10 2.00 35.5 14.7 0.780 72
35.0 495/.3 1.2 11.50 2.00 39.5 16.2 0.554 90
50.0 703/.3 1.4 13.60 2.20 45.5 18.3 0.386 115
70.0 360/.3 1.4 15.30 2.20 51.0 20.0 0.272 143

Note :
We manufacture Round / Flat Cables of 2 ,3 or 4 cores and Winding wires according to individual customer specification. Please write to us with full details of your requirements.

SELECTION GUIDE FOR 3 CORE FLAT CABLES

HP Vs Current

The full load current for Submersible Pump moter - 3 phase, 50 Cycle, 415-425 Volts

HP 5.0 7.5 10.0 12.5 15.0 17.5 20.0 25.0 30.0 35.0
Amp 7.5 11.0 14.9 18.9 22.5 25.2 28.4 35.6 42.3 50.4

Derating Factors

Multiply the current carrying capacity of the cable by factor given below for various ambient temperature

Ambient Temperature °C 30 35 40 45 50
Derating Factor 1.09 1.04 1.00 0.95 0.77